Overall Size Approx. 52,500 m² NLA (Office Floors)
No. of Office Floors 29 floors (12th to 20th, 21st to 29th)
Typical Floor Area Approx. 2,900 m² NLA
Finished Floor-to-Ceiling Height Approx. 2,750 mm
Raised Floor Approx. 180 mm and 330 mm from top of slab to top of raised floor for typical and trading
floors respectively
Planning grid 1,500 mm
Floor Loading Office Floors: Live Load = 34.0 KN/m² ;
Partitions = 1.0 KN/m²
Filing/Compactus Area Approx. 3,500 mm wide strip around the core, 7.5 KN/m²
Curtain Wall Unitised aluminium system with double glazed low E-solar tinted or single thermal toughened glass
Total no. of carparks 713 lots for both towers
Toilets Male and Female, 1 Executive with handicapped and shower facilities
Air-conditioning 24-hour chilled water supply from District Cooling System with 2 AHUs per floor
Estimated cooling load for a typical office floor is approx. 387 kWr per floor
Space available for tenants’ own air-conditioning equipment, subject to availability
Auxiliary cooling water system with emergency power supply back-up
Security System 24-hour CCTV monitoring at all main entrances and exits
Card Access Control, via turnstiles to lift lobbies
Fire Protection Addressable fire alarm system. Automatic sprinkler network, smoke detector system; wet riser system,
hosereels and portable fire extinguishers
Lighting Average 500 lux at desktop level
Incoming Electrical Supply &Electrical Loads 2 separate 22 kV incoming power supply
Lighting:20W/m²
Power: 65 W/m²
Computer Earthing Termination point provided at basement of the building, subject to availability
Standby Generator 20% of estimated tenant normal load
Spare riser For tenants’ inter-floor cabling and specialised services, subject to availability
Space reserved for tenant's own generator set Space available for tenant’s generator, subject to availability. Provision of fuel risers for connection to tenant's generator system
Telecommunication Telephone, Fibre Optic (by service providers) and SCV
Lifts 16 passenger lifts in 2 lifts zones with separate car park lifts (5 nos.) and service lifts (2 nos.)

The above information has been prepared with care. However, it is for guidance purposes only and is subject to change. It cannot form part of an offer or contract. While every reasonable care has been taken in providing this information, Raffles Quay Asset Management Pte Ltd, its subsidiaries, agents or representatives are not responsible for any errors or inaccuracies, or for the consequences of any reliance on such information, whether in the form of costs, claims, expenses, or other losses, and whether direct or indirect.